B-7
B.2 No-fuse Circuit Breaker Chart
For 1-phase/3-phase drives, the current rating of the breaker shall be within 2-4 times rated
input current.
Model
Recommended no-fuse breaker (A)
Fuse Specification
Max. I (A)
Min. I (A)
VFD002E11A
1.6~2.6 times of the rated input current
15 15
VFD004E11A 20
20
VFD007E11A 30
30
VFD002E21A 10
10
VFD004E21A 15
15
VFD007E21A 20
20
VFD015E21A 30
30
VFD022E21A 50
50
VFD002E23A 6
6
VFD004E23A 6
10
VFD007E23A 10
15
VFD015E23A 20
25
VFD022E23A 30
35
VFD037E23A 40
50
VFD055E23A 50
60
VFD075E23A 60
80
VFD110E23A 100
125
VFD150E23A 150
180
VFD004E43A 6
6
VFD007E43A 6
10
VFD015E43A 10
15
VFD022E43A 15
20
VFD037E43A 20
30
VFD055E43A 30
40
VFD075E43A 40
50
VFD110E43A 50
60
VFD150E43A 70
90
VFD185E43A 80
100
VFD220E43A 100
125