Chapter 4 Parameters
4-5
Parameter Explanation
Settings
Factory
Setting
Customer
deceleration (refer
to Accel/Decel time
setting)
1: Auto Accel, Linear Decel
2: Linear Accel, Auto Decel
3: Auto Accel/Decel (Set by load)
4: Auto Accel/Decel (set by Accel/Decel
Time setting)
01.16
Auto acceleration /
deceleration (refer
to Accel/Decel time
setting)
5: Linear Accel. controlled by current, linear
Decel.
0
6: Linear Accel. controlled by current, auto
Decel.
01.17
Acceleration S-
Curve
0.0 to 10.0 / 0.00 to 10.00 sec
0.0
01.18
Deceleration S-
Curve
0.0 to 10.0 / 0.00 to 10.00 sec
0.0
01.19
Accel/Decel Time
Unit
0: Unit: 0.1 sec
0
1: Unit: 0.01 sec
01.20
Delay Time at 0Hz
for Simple Position
0.00 to 600.00 sec
0.00
01.21
Delay Time at 10Hz
for Simple Position
0.00 to 600.00 sec
0.00
01.22
Delay Time at 20Hz
for Simple Position
0.00 to 600.00 sec
0.00
01.23
Delay Time at 30Hz
for Simple Position
0.00 to 600.00 sec
0.00
01.24
Delay Time at 40Hz
for Simple Position
0.00 to 600.00 sec
0.00
01.25
Delay Time at 50Hz
for Simple Position
0.00 to 600.00 sec
0.00
01.26
Maximum Voltage
Frequency (Fbase)
(Motor 1)
0.10 to 599.00 Hz
60.00
01.27
Maximum Output
Voltage (Vmax)
(Motor 1)
115V/230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01.28
Mid-Point
Frequency (Fmid)
(Motor 1)
0
.10 to 599.00 Hz
1.50
01.29
Mid-Point Voltage
(Vmid) (Motor 1)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.30
Minimum Output
Frequency (Fmin)
(Motor 1)
0
.10 to 599.00 Hz
1.50
01.31
Minimum Output
Voltage (Vmin)
(Motor 1)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.32
Maximum Voltage
Frequency (Fbase)
(Motor 2)
0.10 to 599.00 Hz
60.00