B-45
Never connect phase lead capacitors or surge absorbers to the output terminals of the AC motor drive.
If the length is too long, the stray capacitance between cables will increase and may cause
leakage current. It will activate the protection of over current, increase leakage current or not
insure the correction of current display. The worst case is that AC motor drive may damage.
If more than one motor is connected to the AC motor drive, the total wiring length is the sum of the
wiring length from AC motor drive to each motor.