Chapter 4 Parameters
4-76
Group 3: Output Function Parameters
03.00
Multi-function Output Relay (RA1, RB1, RC1)
Factory Setting: 8
03.01
Multi-function Output Terminal MO1
Factory Setting: 1
Settings
Function
Description
0
No Function
1
AC Drive Operational
Active when the drive is ready or RUN command is “ON”.
2
Master Frequency (F)
Attained
Active when the output frequency(H) of AC motor drive
reaches the output frequency(F) setting.
3 Zero
Speed
Active when Command Frequency is lower than the
Minimum Output Frequency.
4
Over-Torque
Detection(OL2)
Active as long as over-torque is detected. (Refer to Pr.06.03
~ Pr.06.05)
5
Baseblock (B.B.)
Indication
Active when the output of the AC motor drive is shut off
during baseblock. Base block can be forced by Multi-function
input (setting 09).
6 Low-Voltage
Indication
Active when low voltage (Lv) is detected.
7
Operation Mode
Indication
Active when operation command is controlled by external
terminal.
8 Fault
Indication
Active when the drive detects abnormal conditions (except
Lv and bb) occurs, the contact will be "closed" (eg.:oc, ov,
oH, oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GFF).
9
Desired Frequency 1
Attained
Active when the desired frequency 1(Pr.03.02) is attained.
10
Terminal Count Value
Attained
Active when the internal counter reaches Terminal Count
Value.
11
Preliminary Count Value
Attained
Active when the internal counter reaches Preliminary Count
Value.