Chapter 2 Installation & Wiring
2-20
Terminal
Symbol
Terminal Function
Factory Settings (NPN mode)
ON: Connect to DCM
DCM Digital
Signal
Common
Common for digital inputs and used for NPN
mode.
RA
Multi-function Relay output
(N.O.) a
Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.03.00 for programming
RB
Multi-function Relay output
(N.C.) b
RC
Multi-function Relay common
MO1
Multi-function Output 1
(Photocoupler)
Maximum 48VDC, 50mA
Refer to Pr.03.01 for programming
MO1-DCM
M o1
M CM
M ax: 48Vdc
50mA
internal circuit
MCM Multi-function
output
common Common for Multi-function Outputs
+10V
Potentiometer power supply
+10VDC 3mA
AVI
Analog voltage Input
ACM
AVI
+10V
internal circuit
AVI circuit
Impedance: 47k
Ω
Resolution: 10
bits
Range:
0 ~ 10VDC =
0 ~ Max. Output Frequency
(Pr.01.00)
Selection: Pr.02.00,
Pr.02.09,
Pr.10.00
Set-up:
Pr.04.11 ~ Pr.04.14, 04.19~04.23
ACM
Analog control signal
(common)
Common for AVI2, ACI, AFM
ACI Analog
current
Input
Impedance: 250
Ω
/100k
Ω
Resolution: 10
bits
Range:
4 ~ 20mA =
0 ~ Max. Output Frequency
(Pr.01.00)
Selection: Pr.02.00,
Pr.02.09,
Pr.10.00