D-72
API
Mnemonic
Operands Function
142
FREQ
P
S1, S2, S3
Speed control of the AC motor drive
Type
OP
Bit Devices
Word devices
Program Steps
X
Y
M K
H KnX KnY KnM T C D FREQ, FREQP: 7 steps
S1
* *
*
S2
* *
*
S3
* *
*
Operands:
S1: frequency command, S2: acceleration time, S3: deceleration time
Explanation:
1.
This command can control frequency command, acceleration time and deceleration time
of the AC motor drive. Please use M1025 to RUN(ON)/STOP(OFF) the AC motor drive
and use M1026 to control the operation direction: FWD(ON)/REV(OFF).
Program Example:
1.
M1025: RUN(ON)/STOP(Off) the AC motor drive. M1026: operation direction of the AC
motor drive – FWD(OFF)/REV(ON). M1015: frequency is reached.
2.
When M10=ON, setting frequency command of the AC motor drive to K300(3.00Hz) and
acceleration/deceleration time is 0.
3.
When M11=ON, setting frequency command of the AC motor drive to K3000(30.00Hz),
acceleration time is 50 and deceleration time is 60.
4.
S2, S3: In the setting of Accel / Decel time, the decimal places are depends on the setting
of Pr01.09. When Pr01.09=1, the unit is 0.01 unit.
As shown in the diagram below, S2(Accelerating time) = 50 which means 0.5sec .
S3(Decelerating time) = 60 which means 0.6sec.
END
M1000
M1025
M11
M1026
FREQP
K300
K0
K0
FREQ
K3000
K50
K60
M11
M10
M10
M11