Chapter 4 Parameters
4-46
00.05
User Defined Coefficient K
Settings
0. 1 to 160.0
Factory Setting: 1.0
The coefficient K determines the multiplying factor for the user-defined unit.
When Pr00.04 is set to 0:
User-defined unit (U) = Output frequency (H) * User Defined Coefficient (K)
When Pr00.04 is set to 16:
User-defined unit (U) = Output frequency (F) * User Defined Coefficient (K)
Or PID frequency setting * User Defined Coefficient (K)
Example:
If user wants to use RPM to display the motor speed when 4-polse motor runs at 60Hz. The
user can display the motor speed by setting Pr.00.04 to 0. The application is shown as follows.
From the formula of motor speed, user-defined unit (U) (RPM) = 60X120/4=1800 (disregard
slip). Therefore, User Defined Coefficient K is 30.0.
NOTE
speed
motor
of
Formula
P
f
n
120
n: speed (RPM) (revolution per minute)
P: pole number of motor
f: operation frequency (Hz)
00.06
Power Board Software Version
Settings
Read
Only
Display
#.##
00.07
Control Board Software Version
Settings
Read
Only
Display
#.##
00.08
Password Input
Settings
0 to 9999
Factory Setting: 0
Display
0~2 (times of wrong password)
The function of this parameter is to input the password that is set in Pr.00.09. Input the correct
password here to enable changing parameters. You are limited to a maximum of 3 attempts.
After 3 consecutive failed attempts, a blinking “codE” will show up to force the user to restart
the AC motor drive in order to try again to input the correct password.
Related parameter: Pr.00.09 (Password Set)