Chapter 4 Parameters
4-23
Parameter Explanation
Settings
Factory
Setting
Customer
07.14
Motor PTC
Overheat Protection
Level
0.1~10.0V 2.4
07.15
Motor PTC
Overheat Warning
Level
0.1~10.0V 1.2
07.16
Motor PTC
Overheat Reset
Delta Level
0.1~5.0V 0.6
07.17
Treatment of the
Motor PTC
Overheat
0: Warn and RAMP to stop
1: Warn and COAST to stop
2: Warn and keep running
0
07.18
Motor Rated Current
(Motor 1)
30 %FLA to 120% FLA
FLA
07.19
Motor No-Load
Current (Motor 1)
0%FLA to 99% FLA
0.4*FLA
07.20
Torque
Compensation
(Motor 1)
0.0 to 10.0
0.0
07.21
Slip Compensation
(Used without PG)
(Motor 1)
0.00 to 10.00
0.00
07.22
Motor Line-to-line
Resistance R1
(Motor 1)
0~65535 m
Ω
0
07.23
Motor Rated Slip
(Motor 1)
0.00 to 20.00 Hz
3.00
07.24
Motor Pole Number
(Motor 1)
2 to 10
4
07.25
Motor Rated Current
(Motor 2)
30 %FLA to 120% FLA
FLA
07.26
Motor No-Load
Current (Motor 2)
0%FLA to 99% FLA
0.4*FLA
07.27
Torque
Compensation
(Motor 2)
0.0 to 10.0
0.0
07.28
Slip Compensation
(Used without PG)
(Motor 2)
0.00 to 10.00
0.00