ASDA-B2-F Parameters
September, 2015
7-49
7
P2-70
MRS
Read Data Format Selection
Address: 028CH
028DH
Operational
Interface:
Panel / Software
Communication
Related
Section:
-
Default: 0
Control
Mode:
ALL
Unit: -
Range: 0x00~0x07
Format: HEX
Data Size: 16-bit
Settings:
Bit 0: Data unit setting of digital input / output (DI / DO); 1: pulse, 0: PUU.
Bit 1: Communication data unit setting; 1: pulse, 0: PUU.
Bit 2: Overflow warning; 1: No overflow warning; 0: Overflow warning, AL289 (PUU) and AL062
(pulse).
Bit 3 ~ Bit 15: Reserved. Must be set to 0.
P2-71
■
CAP
Absolute Position Homing
Address: 028EH
028FH
Operational
Interface:
Panel / Software
Communication
Related
Section:
-
Default: 0
Control
Mode:
ALL
Unit: -
Range: 0 ~ 1
Format: HEX
Data Size: 16-bit
Settings:
When P2-71 is set to 1, the current position will be set as home position. This function can be
enabled only when parameter P2-08 is set to 271.
P2-72~P2-79
Reserved
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Summary of Contents for ASD-B2-0121-F
Page 3: ...September 2015 This page is intentionally left blank...
Page 9: ...VI September 2015 This page is intentionally left blank...
Page 29: ...Installation ASDA B2 F 2 12 September 2015 2 This page is intentionally left blank...
Page 185: ...Parameters ASDA B2 F 7 68 September 2015 7 This page is intentionally left blank...
Page 199: ...Communications ASDA B2 F 8 14 September 2015 8...
Page 201: ...Communications ASDA B2 F 8 16 September 2015 8 This page is intentionally left blank...
Page 217: ...Troubleshooting ASDA B2 F 9 16 September 2015 9 This page is intentionally left blank...
Page 239: ...Absolute System ASDA B2 F 10 22 September 2015 10 This page is intentionally left blank...