ASDA-B2-F Parameters
September, 2015
7-33
7
4. DO.TPOS: It means the position error of the servo drive is within the value of P1-54.
5. DO.MC_OK: It means the position command is completely outputted and the servo finishes
positioning. MC_OK is ON if CMD_OK and TPOS are both ON.
6. DO.MC_OK (remains the digital output status): It is the same as 5. However, once this DO is ON
(7), its status will remain regardless signal 4 is OFF or not.
7. Outputting signal 5 or 6 (Only one can be selected) is determined by parameter P1-48.X.
8. Position deviation: When 7 happens, if 4 (or 5) is OFF, it means the position is deviated and
AL380 can be triggered. Set this alarm via parameter P1-48.Y.
P1-49
SPOKWT Accumulative Time of Speed Reached
Address: 0162H
0163H
Operational
Interface:
Panel / Software
Communication
Related
Section:
Table 7.2
Default: 0
Control
Mode:
Sz
Unit: ms
Range: 0 ~ 65535
Format: DEC
Data Size: 16-bit
Settings:
In speed mode, when the deviation value between speed command and motor feedback speed is
smaller than the range set by P1-47 and reaches the time set by P1-49, DO.SP_OK (DO code is
0x19) will be ON. If the deviation value exceeds the range set by P1-47, it has to recount the time.
P1-50 ~ P1-51
Reserved
P1-52
RES1
Regenerative Resistor Value
Address: 0168H
0169H
Operational
Interface:
Panel / Software
Communication
Related
Section:
2.7
Default:
Determined by the model. Please
refer to the following table.
Control
Mode:
ALL
Unit: Ohm
Range: 5 ~ 750
Format: DEC
Data Size: 16-bit
Settings:
Model
Default (
Ω
)
100 ~ 200 W
100
400 W
100
750 kW
100
1 kW
40
1.5 kW
40
2 kW
20
3 kW
20
Please refer to the description of P1-53 for the setting value when connecting regenerative resistor
with different method.
P1-53
RES2
Regenerative Resistor Capacity
Address: 016AH
016BH
Operational
Interface:
Panel / Software
Communication
Related
Section:
2.7
Default:
Determined by the model. Please
refer to the following table.
Control
Mode:
ALL
Unit: Watt
Range: 0 ~ 6000
Format: DEC
Data Size: 16-bit
Settings:
Model
Default
(
Ω
)
100 ~ 200 W
0
400 W
60
750 kW
60
1 kW
60
Summary of Contents for ASD-B2-0121-F
Page 3: ...September 2015 This page is intentionally left blank...
Page 9: ...VI September 2015 This page is intentionally left blank...
Page 29: ...Installation ASDA B2 F 2 12 September 2015 2 This page is intentionally left blank...
Page 185: ...Parameters ASDA B2 F 7 68 September 2015 7 This page is intentionally left blank...
Page 199: ...Communications ASDA B2 F 8 14 September 2015 8...
Page 201: ...Communications ASDA B2 F 8 16 September 2015 8 This page is intentionally left blank...
Page 217: ...Troubleshooting ASDA B2 F 9 16 September 2015 9 This page is intentionally left blank...
Page 239: ...Absolute System ASDA B2 F 10 22 September 2015 10 This page is intentionally left blank...