
•
•
•
•
•
•
Parameter 1-34 Rotor Leakage Reactance (X2)
Table 87: Parameter 1-34 Rotor Leakage Reactance (X2)
1-34 Rotor Leakage Reactance (X2)
Default value: Size related
Parameter type: Range, 0.0400 - 400.0000 Ohm
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: False
N O T I C E
This parameter is only relevant for asynchronous motors.
Set the rotor leakage reactance of the motor using 1 of these methods:
Run an AMA on a cold motor. The drive measures the value from the motor.
Enter the X
2
value manually. Obtain the value from the motor supplier.
Use the X
2
default setting. The drive establishes the setting based on the motor nameplate data.
N O T I C E
The parameter value is updated after each torque calibration if option
[3] 1st start with store
or option
[4] Every start with store
is
selected in
parameter 1-47 Torque Calibration
.
Parameter 1-35 Main Reactance (Xh)
Table 88: Parameter 1-35 Main Reactance (Xh)
1-35 Main Reactance (Xh)
Default value: Size related
Parameter type: Range, 1.0000 - 10000.0000 Ohm]
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
Parameter 1-35 Main Reactance (Xh)
does not have effect when
parameter 1-10 Motor Construction
is set to
[1] PM, non-salient SPM
.
Set the main reactance of the motor using 1 of these methods:
Run an AMA on a cold motor. The drive measures the value from the motor.
Enter the X
h
value manually. Obtain the value from the motor supplier.
Use the X
h
default setting. The drive establishes the setting based on the motor nameplate data.
N O T I C E
The parameter value is updated after each torque calibration if option
[3] 1st start with store
or option
[4] Every start with store
is
selected in
parameter 1-47 Torque Calibration
.
AU275636650261en-000101 / 130R0334 | 83
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide
Summary of Contents for VLT AutomationDrive FC 301
Page 2: ......