N O T I C E
The following parameters are only available in FC 302:
Parameter 1-02 Flux Motor Feedback Source
Parameter 1-07 Motor Angle Offset Adjust
Parameter 1-00 Configuration Mode
Table 58: Parameter 1-00 Configuration Mode
1-00 Configuration Mode
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the application control principle to be used when a remote reference (that is via analog input or fieldbus) is active. A remote
reference can only be active when
parameter 3-13 Reference Site
is set to
[0] Linked to Hand/Auto
or
[1] Remote
.
Op-
tion
Name
Description
[0]
Speed open
loop
Enables speed control (without feedback signal from motor) with automatic slip compensation for
almost constant speed at varying loads. Compensations are active, but can be disabled in
parameter
group 1-** Load and Motor
. Set the speed control parameters in
parameter group 7-0* Speed PID Ctrl
.
[1]
Speed closed
loop
Enables speed closed-loop control with feedback. Obtain full holding torque at 0 RPM. For increased
speed accuracy, provide a feedback signal and set the speed PID control. Set the speed control pa-
rameters in
parameter group 7-0* Speed PID Ctrl
.
[2]
Torque
N O T I C E
This option is only available in FC 302.
Enables torque closed-loop control with feedback. Only possible when
parameter 1-01 Motor Control
Principle
is set to
[3] Flux w/motor feedb
.
[3]
Process
Enables the use of process control in the drive. Set the process control parameters in
parameter
groups 7-2* Process Ctrl. Feedb.
and
7-3* Process PID Ctrl
.
[4]
Torque open
loop
Enables the use of torque open-loop mode (
parameter 1-01 Motor Control Principle
). Set the torque
PID parameters in
parameter group 7-1* Torque PI Control
.
[5]
Wobble
Enables the wobble functionality in
parameter 30-00 Wobble Mode
to
parameter 30-19 Wobble Delta
Freq. Scaled
.
[6]
Surface winder
Enables the surface winder control-specific parameters in
parameter groups 7-2* Process Ctrl. Feedb.
and
7-3* Process PID Ctrl.
[7]
Extended PID
speed OL
Specific parameters in
parameter groups 7-2* Process Ctrl. Feedb.
to
7-5* Ext. Process PID Ctrl.
[8]
Extended PID
speed CL
Specific parameters in
parameter groups 7-2* Process Ctrl. Feedb.
to
7-5* Ext. Process PID Ctrl.
[9]
Positioning
N O T I C E
This option is only available with software version 48.XX.
Activates positioning mode.
AU275636650261en-000101 / 130R0334 | 63
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide