Failure
Alarm Element in param-
eter 14-90 Fault
Level
Off Warning Trip Trip lock Trip with de-
layed reset
Fan contactor
431
1490.25
–
–
X
D
–
Inrush fault
33
1490.26
X
X
X
D
X
Fieldbus fault
34
1490.27
X
D
–
–
–
1
In small and medium power drives,
alarm 69, Power card temperature
is only a warning.
2
Only high-power drives.
3
Warning 59 is configured in 1490.19. The current limit warning can be disabled by choice. The alarm cannot be configured.
VLT® Motion Control Tool MCT 10 has the element numbers listed in the column ID. Use this table with MCT 10 to get information
about specific fault levels.
5.15 Parameter Group 15-** Drive Information
5.15.1 15-0* Operating Data
Parameter 15-00 Operating Hours
Table 761: Parameter 15-00 Operating Hours
15-00 Operating Hours
Default value: 0 h
Parameter type: Range, 0 - 2147483647 h
Setup: All setups
Conversion index: 74
Data type: Uint32
Change during operation: False
View for how many hours the drive has run. The value is saved when the drive is turned off.
Parameter 15-01 Running Hours
Table 762: Parameter 15-01 Running Hours
15-01 Running Hours
Default value: 0 h
Parameter type: Range, 0 - 2147483647 h
Setup: All setups
Conversion index: 74
Data type: Uint32
Change during operation: False
View how many hours the motor has run. Reset the counter in
parameter 15-07 Reset Running Hours Counter
. The value is saved
when the drive is turned off.
Parameter 15-02 kWh Counter
Table 763: Parameter 15-02 kWh Counter
15-02 kWh Counter
Default value: 0 kWh
Parameter type: Range, 0 - 2147483647 kWh
Setup: All setups
Conversion index: 75
Data type: Uint32
Change during operation: False
Register the power consumption of the motor as an average value over 1 hour. Reset the counter in
parameter 15-06 Reset kWh
Counter
.
AU275636650261en-000101 / 130R0334 | 477
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide