Bit Hex
Dec
Warning word
Warning word 2
Warning word 3
Parameter 16-92 Warning Word Parameter 16-93 Warning
Word 2
Parameter 16-98 Warning Word
3
28
10000000 268435456
Encoder loss (W90)
Reserved
Load S2
29
20000000 536870912
Output freq. lim. (W62)
BackEMF too high
Load
30
40000000 1073741824 Safe stop (W68)
PTC thermistor (W74)
Stator S2
31
80000000 2147483648 Extended status word
–
Stator
Table 1438: Description of Extended Status Word
Bit Hex
Dec
Ext. status word
Ext. status word 2
Ext. status
word 3
Parameter 16-94 Ext. Status Word
Parameter 16-95 Ext.
Status Word 2
Parameter
16-99 Ext.
Status Word 3
Extended Status Word
0
00000001 1
Ramping
Off
High pres-
sure stop
1
00000002 2
AMA running
Hand/auto
Low pressure
stop
2
00000004 4
Start CW/CCW
start_possible is active, when the DI selections [12] OR
[13] are active and the requested direction matches
the reference sign
Profibus OFF1 active
Defrost
3
00000008 8
Slow down
slow down command active, for example via CTW bit
11 or DI
Profibus OFF2 active
Pre/post
lube
4
00000010 16
Catch up
catch up command active, for example via CTW bit 12
or DI
Profibus OFF3 active
User-defined
alerts
5
00000020 32
Feedback high
feedback >
parameter 4-57 Warning Feedback High
Relay 123 active
–
6
00000040 64
Feedback
low feedback <
parameter 4-56 Warning Feedback Low
Start prevented
–
7
00000080 128
Output current high
current >
parameter 4-51 Warning Current High
Control ready
–
8
00000100 256
Output current low
current <
parameter 4-50 Warning Current Low
Drive ready
–
9
00000200 512
Output freq high
speed >
parameter 4-53 Warning Speed High
Quick stop
–
10
00000400 1024
Output freq low
DC brake
–
AU275636650261en-000101 / 130R0334
698 | Danfoss A/S © 2022.12
Troubleshooting
VLT AutomationDrive FC 301/302
Programming Guide
Summary of Contents for VLT AutomationDrive FC 301
Page 2: ......