Parameter 7-44 Process PID Gain Scale at Max. Ref.
Table 475: Parameter 7-44 Process PID Gain Scale at Max. Ref.
7-44 Process PID Gain Scale at Max. Ref.
Default value: -100%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Enter a scaling percentage to apply to the process PID output when operating at the maximum reference. The scaling percentage is
adjusted linearly between the scale at minimum reference (
parameter 7-43 Process PID Gain Scale at Min. Ref.
) and the scale at maxi-
mum reference (
parameter 7-44 Process PID Gain Scale at Max. Ref.
).
Parameter 7-45 Process PID Feed Fwd Resource
Table 476: Parameter 7-45 Process PID Feed Fwd Resource
7-45 Process PID Feed Fwd Resource
Default value: [0] No function
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option Name
Description
[0]*
No function
Select which drive input should be used as the feed-forward factor. The factor is added to the
output of the PID controller. This increases dynamic performance.
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
N O T I C E
This option is only available in FC 302.
[8]
Frequency input 33
[11]
Local bus reference
[20]
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[29]
Analog input X48/2
[32]
Bus PCD
N O T I C E
This option is only available in FC 302.
Selects a fieldbus reference configured by
parameter 8-02 Control Word Source
. Change
parame-
ter 8-42 PCD Write Configuration
for the bus used to make the feed forward available in
parame-
ter 7-48 PCD Feed Forward
. Use index 1 for feed forward [748] (and index 2 for reference [1682]).
AU275636650261en-000101 / 130R0334 | 265
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide