Option Name
Description
[121]
Remote ref active
Output is high when
parameter 3-13 Reference Site
=
[1] Remote
or
[0] Linked to hand/auto while
the LCP
.
[122]
No alarm
Output is high when no alarm is present.
[123]
Start command ac-
tive
Output is high when the start command is high (that is via digital input, bus connection, [Hand
On], or [Auto On]), and a stop has been the last command.
[124]
Running reverse
Output is high when the drive is running counterclockwise (the logical product of the status bits
running AND reverse).
[125]
Drive in hand mode
Output is high when the drive is in hand-on mode (as indicated by the LED light above [Hand
On]).
[126]
Drive in auto mode
Output is high when the drive is in auto-on mode (as indicated by LED light on above [Auto
On]).
[151]
ATEX ETR cur. alarm
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
.
If
alarm 164, ATEX ETR cur.lim.alarm
is active, the output is 1.
[152]
ATEX ETR freq.
alarm
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
.
If
alarm 166, ATEX ETR freq.lim.alarm
is active, the output is 1.
[153]
ATEX ETR cur. warn-
ing
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
.
If
alarm 163, ATEX ETR cur.lim.warning
is active, the output is 1.
[154]
ATEX ETR freq.
warning
Selectable if
parameter 1-90 Motor Thermal Protection
is set to
[20] ATEX ETR
or
[21] Advanced ETR
.
If
warning 165, ATEX ETR freq.lim.warning
is active, the output is 1.
[173]
10Wh counter pulse
[178]
RS Flipflop 8
See
parameter group 13-1* Comparators
.
[179]
RS Flipflop 9
See
parameter group 13-1* Comparators
.
[180]
Clock fault
[181]
Prev. Maintenance
[188]
AHF Capacitor Con-
nect
[189]
External Fan Control The internal logics for the internal fan control is transferred to this output to make it possible to
control an external fan (relevant for hp duct cooling).
[190]
Safe Function active
[191]
Safe Opt. Reset req.
[192]
RS Flipflop 0
See
parameter group 13-1* Comparators
.
[193]
RS Flipflop 1
See
parameter group 13-1* Comparators
.
[194]
RS Flipflop 2
See
parameter group 13-1* Comparators
.
[195]
RS Flipflop 3
See
parameter group 13-1* Comparators
.
[196]
RS Flipflop 4
See
parameter group 13-1* Comparators
.
[197]
RS Flipflop 5
See
parameter group 13-1* Comparators
.
[198]
RS Flipflop 6
See
parameter group 13-1* Comparators
.
AU275636650261en-000101 / 130R0334
214 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide