N O T I C E
This parameter is only valid with sofware version 48.XX.
Shows the actual position error in position units defined in
parameter group 17-7* Position Scaling
. Position error is the difference
between the actual position and the commanded position. The position error is the input for the position PI controller.
Parameter 16-09 Customer Readout
Table 830: Parameter 16-09 Customer Readout
16-09 Customer Readout
Default value: 0 CustomReadoutUnit Parameter type: Range, 0 CustomReadoutUnit -
999999.99 CustomReadoutUnit
Setup: All setups
Conversion index: -2
Data type: Int32
Change during operation: False
View the value of custom readout from
parameter 0-30 Unit for Userdefined Readout
to
parameter 0-32 Custom Readout Max Value
.
5.16.2 16-1* Motor Status
N O T I C E
The following parameter is only available in FC 302:
Parameter 16-24 Calibrated Stator Resistance
Parameter 16-10 Power [kW]
Table 831: Parameter 16-10 Power [kW]
16-10 Power [kW]
Default value: 0 kW
Parameter type: Range, 0 - 10000 kW
Setup: All setups
Conversion index: 1
Data type: Int32
Change during operation: False
Shows motor power in kW. The value shown is calculated based on the actual motor voltage and motor current. The value is fil-
tered, and therefore approximately 1.3 s may pass from when an input value changes to when the data readout values change. The
resolution of readout value on fieldbus is in 10-W steps. The base unit is in W.
Parameter 16-11 Power [hp]
Table 832: Parameter 16-11 Power [hp]
16-11 Power [hp]
Default value: 0 hp
Parameter type: Range, 0 - 10000 hp
Setup: All setups
Conversion index: -2
Data type: Int32
Change during operation: False
Shows motor power in hp. The value shown is calculated based on the actual motor voltage and motor current. The value is filtered,
and therefore approximately 1.3 ms may pass from when an input value changes to when the data readout values change.
Parameter 16-12 Motor Voltage
Table 833: Parameter 16-12 Motor Voltage
16-12 Motor Voltage
Default value: 0 V
Parameter type: Range, 0 - 6000 V
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: False
View the motor voltage, a calculated value used for controlling the motor.
AU275636650261en-000101 / 130R0334
498 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide