Option
Function
[223] On target
N O T I C E
This option is only available with software version 48.XX.
Positioning is completed and the on-target signal is sent when the actual position is within
pa-
rameter 3-05 On Reference Window
for the duration of
parameter 3-09 On Target Time
and the ac-
tual speed does not exceed
parameter 3-05 On Reference Window
.
[224] Position limit
N O T I C E
This option is only available with software version 48.XX.
The position error exceeds the value in
parameter 4-71 Maximum Position Error
for the time set in
parameter 4-72 Position Error Timeout
.
[225] Position error
N O T I C E
This option is only available with software version 48.XX.
The position is outside the limits set in
parameter 3-06 Minimum Position
and
parameter 3-07 Maxi-
mum Position
.
[226] Touch on target
N O T I C E
This option is only available with software version 48.XX.
The target position is reached in touch probe position mode.
[227] Touch activated
N O T I C E
This option is only available with software version 48.XX.
Touch probe positioning is active. The drive monitors the touch probe sensor input.
[228] Touch sensor found
N O T I C E
This option is only available with software version 48.XX.
The touch sensor has been detected.
[229] Vir. master on ref.
N O T I C E
This option is only available with software version 48.XX.
The virtual master is running on the set reference.
[231] In power lim. mot.
[232] In power lim. gen.
[233] In power limit
[234] PE power off
AU275636650261en-000101 / 130R0334
204 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide