Parameter 8-37 Max Inter-Char Delay
Table 516: Parameter 8-37 Max Inter-Char Delay
8-37 Max Inter-Char Delay
Default value: Size related
Parameter type: Range, 0.00 - 35.00 ms
Setup: 1 setup
Conversion index: -5
Data type: Uint16
Change during operation: True
Specify the maximum allowed time interval between receipt of 2 bytes. This parameter activates timeout if transmission is interrup-
ted. This parameter is active only when
parameter 8-30 Protocol
is set to
[1] FC MC protocol
.
Parameter 8-39 Protocol/Profile Firmware Version
Table 517: Parameter 8-39 Protocol/Profile Firmware Version
8-39 Protocol/Profile Firmware Version
Default value: 0
Parameter type: Range, 0 - 10, Array [8]
Setup: All setups
Conversion index: 0
Data type: VisibleString [10]
Change during operation: False
This parameter shows the firmware revision as follows:
Index [0] = FC
Index [1] = Modbus
Index [2] = Metasys N2
Index [3] = FLN
Index [4] = BACnet
Index [5] = Future native protocol
Index [6] = PROFIdrive profile
Index [7] = DS402 profile
5.9.5 8-4* FC MC Protocol Set
Parameter 8-40 Telegram Selection
Table 518: Parameter 8-40 Telegram Selection
8-40 Telegram Selection
Default value: [1] Standard telegram 1
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[1]*
Standard telegram 1
Enables use of freely configurable telegrams or standard telegrams for the FC port.
[100]
None
[101]
PPO 1
[102]
PPO 2
[103]
PPO 3
[104]
PPO 4
[105]
PPO 5
[106]
PPO 6
[107]
PPO 7
AU275636650261en-000101 / 130R0334 | 289