Parameter 17-58 Encoder Sim. Resolution Adv.
Table 934: Parameter 17-58 Encoder Sim. Resolution Adv.
17-58 Encoder Sim. Resolution Adv.
Default value: 0
Parameter type: Range, 0 - 16384
Setup: 1 setup
Conversion index: 0
Data type: Uint16
Change during operation: False
Set the encoder simulation resolution as a continuous value in steps of 1. This parameter is only active when
[5] Enable encoder sim.
adv.
is selected in
parameter 17-56 Encoder Sim. Resolution
.
Parameter 17-59 Resolver Interface
Table 935: Parameter 17-59 Resolver Interface
17-59 Resolver Interface
Default value: [0] Disabled
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: False
Activate the VLT® Resolver Input MCB 103 when the resolver parameters are selected. To avoid damage to resolvers, adjust
parame-
ter 17-50 Poles
and
parameter 17-53 Transformation Ratio
before enabling this parameter.
Option
Name
Description
[0]*
Disabled
[1]
512
5.17.6 17-6* Monitoring and Application
N O T I C E
The following parameters are only available in FC 302:
Parameter 17-67 Raw Inc. Quad Counter
Parameter 17-68 Raw Abs. Pos. Low
Parameter 17-69 Raw Abs. Pos. High
This parameter group is for selecting extra functions when VLT® Encoder MCB 102 or VLT® Resolver Input MCB 103 is fitted into
option slot B as speed feedback. Monitoring and application parameters cannot be adjusted while the motor is running.
Parameter 17-60 Feedback Direction
Table 936: Parameter 17-60 Feedback Direction
17-60 Feedback Direction
Default value: [0] Clockwise
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Change the detected encoder rotation direction without changing the wiring to the encoder.