Option Name
Description
20 mA × 22
A
38 . 4
A
= 11 . 46 mA
When the normal motor current is equal to 20 mA, the output setting of
parameter 6-52 Terminal
42 Output Max Scale
is:
I
VLT, MAX
× 100
I
Motor, Nom
= 38 . 4 × 100
22
= 175 %
[104]
Torque rel to limit
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
.
[105]
Torque relate to
rated
The torque is related to the motor torque setting.
[106]
Power
Taken from
parameter 1-20 Motor Power [kW]
.
[107]
Speed
Taken from
parameter 3-03 Maximum Reference
. 20 mA equals the value in
parameter 3-03 Maxi-
mum Reference
.
[108]
Torque
Torque reference related to 160% torque.
[109]
Max out freq
0 Hz = 0 mA,
parameter 4-19 Max Output Frequency
= 20 mA.
[113]
PID clamped out-
put
[117]
Shaft power
[119]
Torque % lim
[123]
Speed both dir
[135]
Torq.% nom 4–
20mA
The torque setting is related to the motor torque setting.
[139]
Bus ctrl
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[141]
Bus ctrl t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in case of field-
bus timeout.
[147]
Main act val
[158]
Motor Volt.
Parameter 36-51 Terminal X49/9 Digital Output
Table 1337: Parameter 36-51 Terminal X49/9 Digital Output
36-51 Terminal X49/9 Digital Output
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
No operation
[1]
Control ready
[2]
Drive ready
AU275636650261en-000101 / 130R0334
650 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide