Parameter 35-01 Term. X48/4 Input Type
Table 1280: Parameter 35-01 Term. X48/4 Input Type
35-01 Term. X48/4 Input Type
Default value: [0] Not connected
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
View the temperature sensor type detected at input X48/4.
Option
Name
Description
[0]*
Not connected
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
Parameter 35-02 Term. X48/7 Temperature Unit
Table 1281: Parameter 35-02 Term. X48/7 Temperature Unit
35-02 Term. X48/7 Temperature Unit
Default value: [60] °C
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Select the unit to be used with temperature input X48/7 settings and readouts.
Option
Name
Description
[60]*
°C
[160]
°F
Parameter 35-03 Term. X48/7 Input Type
Table 1282: Parameter 35-03 Term. X48/7 Input Type
35-03 Term. X48/7 Input Type
Default value: [0] Not connected
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
View the temperature sensor type detected at input X48/7.
Option
Name
Description
[0]*
Not connected
[1]
PT100 2-wire