Parameter 42-54 Ramp Down Time
Table 1402: Parameter 42-54 Ramp Down Time
42-54 Ramp Down Time
Default value: 1 s
Parameter type: Range, 0.1 - 3600 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
Ramp-down time for the start ramp.
5.31.7 42-7* SMS
Parameter 42-70 Activation
Table 1403: Parameter 42-70 Activation
42-70 Activation
Default value: [0] Inactive
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: False
Option
Name
Description
[0]*
Inactive
[1]
Active
Parameter 42-71 Cut Off Speed
Table 1404: Parameter 42-71 Cut Off Speed
42-71 Cut Off Speed
Default value: 1500 RPM
Parameter type: Range, 120 - 20000 RPM
Setup: 2 setups
Conversion index: 67
Data type: Uint16
Change during operation: False
Maximum allowed speed.
5.31.8 42-8* Status
Parameter 42-80 Safe Option Status
Table 1405: Parameter 42-80 Safe Option Status
42-80 Safe Option Status
Default value: 0
Parameter type: Range, 0 - 4294967295
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Shows the safety option status word as a hexadecimal value.
Parameter 42-81 Safe Option Status 2
Table 1406: Parameter 42-81 Safe Option Status 2
42-81 Safe Option Status 2
Default value: 0
Parameter type: Range, 0 - 2147483647
Setup: 1 setup
Conversion index: 0
Data type: Uint32
Change during operation: True
Shows the safety option status word 2 as a hexadecimal value. For example, it contains DI1, DI2, and blank initial state status.
AU275636650261en-000101 / 130R0334
676 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide