N O T I C E
This parameter cannot be adjusted while the motor is running.
Option
Name
Description
[0]*
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
Parameter 5-02 Terminal 29 Mode
Table 325: Parameter 5-02 Terminal 29 Mode
5-02 Terminal 29 Mode
Default value: [0] Input
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
5.6.2 5-1* Digital Inputs
N O T I C E
The following parameter is only available in FC 302:
Parameter 5-13 Terminal 29 Digital Input
The digital inputs are used for selecting various functions in the drive. Refer to
for functions which can be assigned to
digital inputs.
Functions in function group 1 have higher priority than functions in function group 2.
Table 326: Function Groups
Group
Functions
1
Reset, coast stop, reset, and coast stop, quick stop, DC brake, stop, and the [Off] key.
2
Start, latched start, reversing, start reversing, jog, and freeze output.
Table 327: Digital Input Functions and Terminals
Digital input function
Select
Terminal
No operation
[0]
All, terminal 32, 33
Reset
[1]
All
Coast inverse
[2]
All, terminal 27
Coast and reset inverse
[3]
All
Quick stop inverse
[4]
All
DC brake inverse
[5]
All
Stop inverse
[6]
All
AU275636650261en-000101 / 130R0334
176 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302