N O T I C E
This parameter is only available with software version 48.XX.
Select the trigger for the homing synchronization function. Only active when
[2] Home Sync Function
is selected in
parameter 17-80
Homing Function
. The homing synchronization function sets the actual position to the value of
parameter 17-82 Home Position
:
Index 0 if the homing sensor is approached in the forward direction.
Index 1if the homing sensor is approached in the reverse direction.
Option Name
Description
[0]*
1st time after power
After power-up, the 1
st
detection of the homing sensor triggers the function.
[1]
1st t. aft.pow. forward After power-up, the 1
st
detection of the homing sensor in the forward direction triggers the
function.
[2]
1st t. aft.pow. reverse
After power-up, the 1
st
detection of the homing sensor in the reverse direction triggers the
function.
[3]
1st time after start
After start, the 1
st
detection of the homing sensor triggers the function.
[4]
1st t. aft.str. forward
After start, the 1
st
detection of the homing sensor in the forward direction triggers the func-
tion.
[5]
1st t. aft.str. reverse
After start, the 1
st
detection of the homing sensor in the reverse direction triggers the function.
[6]
Every time
Every detection of the homing sensor triggers the function.
[7]
Every time forward
Every detection of the homing sensor in the forward direction triggers the function.
[8]
Every time reverse
Every detection of the homing sensor in the reverse direction triggers the function.
Parameter 17-82 Home Position
Table 952: Parameter 17-82 Home Position
17-82 Home Position
Default value: 0 Custom- ReadoutU-
nit2
Parameter type: Range, -2147483648 - 2147483647
CustomReadoutUnit2, Array [2]
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
N O T I C E
This parameter is only available with software version 48.XX.
Set the homing position in position units defined in
parameter group 17-7* Position Scaling
. This is an array parameter with 2 ele-
ments. Indices in this parameter have a different meaning in the following situations:
If
parameter 17-80 Homing Function
is set to options [10]–[13], index 0 of this parameter defines the actual home position and
index 1 is used as the homing offset, which defines where to stop.
If
parameter 17-80 Homing Function
is set to
[2] Home Sync Function
, and
parameter 17-81 Home Sync Function
is set to
[0] 1st time
after power
,
[3] 1st time after start
, or
[6] Every time
, then indices have the following meaning:
Index 0 is the homing position when the homing sensor is approached in the forward direction.
Index 1 is the homing position when the homing sensor is approached in the reverse direction.
AU275636650261en-000101 / 130R0334 | 531
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide