Option Name
Description
[137]
Speed 4–20mA
Taken from
parameter 3-03 Maximum Reference
. 20 mA = value in
parameter 3-03 Maximum Refer-
ence
.
[138]
Torque 4–20mA
Torque reference related to 160% torque.
[139]
Bus ctrl.
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[140]
Bus ctrl. 4–20mA
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[141]
Bus ctrl t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in case of field-
bus timeout.
[142]
Bus ctrl 4-20mA
t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in case of field-
bus timeout.
[147]
Main act val
[148]
Main act val
4-20mA
[149]
Torque % lim
4-20mA
Analog output at 0 torque is 12 mA. Motoring torque increases the output current to maximum
torque limit 20 mA (set in
parameter 4-16 Torque Limit Motor Mode
). Generating torque decreases
the output to torque limit in generator mode (set in
parameter 4-17 Torque Limit Generator Mode
)
Example:
Parameter 4-16 Torque Limit Motor Mode
= 200% and
parameter 4-17 Torque Limit Genera-
tor Mode
= 200%. 20 mA = 200% motoring and 4 mA = 200% generating.
[150]
Max Out Fr
4-20mA
0 Hz = 0 mA,
parameter 4-19 Max Output Frequency
= 20 mA.
[158]
Motor Volt.
[159]
Motor Volt.
4-20mA
Parameter 6-71 Terminal X45/1 Min. Scale
Table 437: Parameter 6-71 Terminal X45/1 Min. Scale
6-71 Terminal X45/1 Min. Scale
Default value: 0%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Scale the minimum output of the selected analog signal at terminal X45/1 as a percentage of the maximum signal value. For exam-
ple, if 0 mA (or 0 Hz) is required at 25% of the maximum output value, then program 25%. Scaling values up to 100% can never
exceed the corresponding setting in
parameter 6-72 Terminal X45/1 Max. Scale
.
Parameter 6-72 Terminal X45/1 Max. Scale
Table 438: Parameter 6-72 Terminal X45/1 Max. Scale
6-72 Terminal X45/1 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Scale the maximum output of the selected analog signal at terminal X45/1. Set the value to the maximum value of the current signal
output. Scale the output to give a current lower than 20 mA at full scale, or 20 mA at an output below 100% of the maximum signal
value. If 20 mA is the required output current at a value between 0–100% of the full-scale output, program the percentage value in
AU275636650261en-000101 / 130R0334
248 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide