Parameter 17-51 Input Voltage
Table 930: Parameter 17-51 Input Voltage
17-51 Input Voltage
Default value: 7 V
Parameter type: Range, 2 - 8 V
Setup: 1 setup
Conversion index: -1
Data type: Uint8
Change during operation: False
Set the input voltage to the resolver. The voltage is stated as RMS value. The value is stated in the datasheet for resolvers.
Parameter 17-52 Input Frequency
Table 931: Parameter 17-52 Input Frequency
17-52 Input Frequency
Default value: 10 kHz
Parameter type: Range, 2 - 15 kHz
Setup: 1 setup
Conversion index: 2
Data type: Uint8
Change during operation: False
Set the input frequency to the resolver. The value is stated in the datasheet for resolvers.
Parameter 17-53 Transformation Ratio
Table 932: Parameter 17-53 Transformation Ratio
17-53 Transformation Ratio
Default value: 0.5
Parameter type: Range, 0.1 - 1.1
Setup: 1 setup
Conversion index: -1
Data type: Uint8
Change during operation: False
Set the transformation ratio for the resolver. The transformation ratio is:
T
ratio
=
V
out
V
in
The value is stated in the datasheet for resolvers.
Parameter 17-56 Encoder Sim. Resolution
Table 933: Parameter 17-56 Encoder Sim. Resolution
17-56 Encoder Sim. Resolution
Default Value: [0] Disabled
Parameter Type: Option
Setup: All setups
Conversion Index: -
Data Type: Uint8
Change during operation: False
Set the resolution and activate the encoder emulation function (generation of encoder signals from the measured position from a
resolver). Use this function to transfer the speed or position information from 1 drive to another. To disable the function, select
[0]
Disabled
.
Option
Name
Description
[0]*
Disabled
[1]
512
[2]
1024
[3]
2048
[4]
4096
[5]
Enable encoder sim. adv.
Set the encoder simulation resolution via
parameter 17-58 Encoder Sim. Resolution Adv
.
AU275636650261en-000101 / 130R0334
522 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide
Summary of Contents for VLT AutomationDrive FC 301