The following events are logged:
W200 - Emergency mode.
W201 - Emerg. M mode was act. (deactivated).
W202 - Emerg. M limits exceeded covered by the activated critical alarm number.
(W280) - Emcy M service warning - service is needed.
(W281) - Emcy OPR unexpected - emergency mode does not work as expected.
All alarms are logged as usual, and critical emergency mode alarms are logged in the emergency mode log in
parameter group 18-1*
Emergency Mode Log
.
N O T I C E
During emergency-mode operation, all stop commands to the drive are ignored, including coast/coast inverse and external inter-
lock. The keypad is also locked during emergency mode to prevent user interference during operation of the safety system. How-
ever, if Safe Torque Off is available in the drive, this function is still active.
N O T I C E
Emergency mode has a special live zero function for handling lost analog signal inputs used for emergency mode setpoint/feed-
back, for example, for handling a burnt cable. How emergency mode should continue in these live zero situations is configured in
parameter 6-02 Emergency Mode Live Zero Timeout Function
. If live zero is activated,
Emergency mode not working as expected
is
activated so that a redundant system can take over or a setup change can be activated. A warning for live zero has a higher
priority than the warning
Emergency mode
and will replace that information in the display.
N O T I C E
If setting the command
[11] Start Reversing
on a digital input terminal in
parameter 5-10 Terminal 18 Digital Input
, the drive under-
stands this as a reversing command.
Parameter 24-00 Emergency Mode Function
Table 1037: Parameter 24-00 Emergency Mode Function
24-00 Emergency Mode Function
Default value: [0] Disabled
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
N O T I C E
Alarms are produced or ignored in accordance with the selection in
parameter 24-09 Emergency Mode Alarm Handling
.
Option Name
Description
[0]*
Disabled
The emergency-mode function is not active.
[1]
Enabled-run for-
ward
In this mode, the motor continues to operate in a clockwise direction. Works only in open loop.
Set
parameter 24-01 Emergency Mode Configuration
to
[0] Open Loop
.
[2]
Enable-run re-
verse
In this mode, the motor continues to operate in a counterclockwise direction. Works only in open
loop. Set
parameter 24-01 Emergency Mode Configuration
to
[0] Open Loop
.
[3]
Enabled-coast
In this mode, the output is disabled, and the motor is allowed to coast to stop.
[4]
Enable-run
Fwd/Rev
[8]
Alarm suppres-
sion
In this mode, the drive continues operation as normal, meaning on standard parameters and con-
trol operation, but where the alarms are suppressed as in normal emergency mode. The emcy LCP
AU275636650261en-000101 / 130R0334 | 563
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide