Number Description
Warning Alarm/trip Alarm/trip
lock
Parameter reference
69
Pwr. card temp
–
X
X
–
70
Illegal FC configuration
–
–
X
–
73
Safe stop auto restart
(X)
(X)
–
Parameter 5-19 Terminal 37 Safe Stop
76
Power unit setup
X
–
–
–
77
Reduced power mode
X
–
–
Parameter 14-59 Actual Number of Inver-
ter Units
78
Tracking error
(X)
(X)
–
Parameter 4-34 Tracking Error Function
79
Illegal PS config
–
X
X
–
80
Drive Initialized to default value
–
X
–
–
81
CSIV corrupt
–
X
–
–
82
CSIV parameter error
–
X
–
–
83
Illegal option combination
–
–
X
–
88
Option detection
–
–
X
–
89
Mechanical brake sliding
X
–
–
–
90
Feedback monitor
(X)
(X)
–
Parameter 17-61 Feedback Signal Moni-
toring
91
Analog input 54 wrong settings
–
–
X
S202
99
Locked rotor
–
X
X
–
101
Speed monitor
X
X
–
–
104
Mixing fans
X
X
–
–
122
Mot. rotat. unexp.
–
X
–
–
123
Motor mod. changed
–
X
–
–
157
Power limit mot.
–
X
–
Parameter 4-80 Power Limit Func. Motor
Mode
,
parameter 4-82 Power Limit Motor
Mode
158
Power limit gen.
–
X
–
Parameter 4-81 Power Limit Func. Genera-
tor Mode
,
parameter 4-83 Power Limit
Generator Mode
200
Emergency mode
X
–
–
201
Emerg. m was active
X
–
–
202
Emerg. m limits exceeded
X
–
–
210
Position tracking
X
X
–
Parameter 4-70 Position Error Function
,
parameter 4-71 Maximum Position Error
,
parameter 4-72 Position Error Timeout
AU275636650261en-000101 / 130R0334
694 | Danfoss A/S © 2022.12
Troubleshooting
VLT AutomationDrive FC 301/302
Programming Guide