Option
Name
Description
[0]
Off
Disables DC-link compensation.
[1]*
On
Enables DC-link compensation.
[2]
Advanced
Improved compensation of DC-link ripple caused by mains frequency and phase imbalance.
N O T I C E
Parameter 0-03 Regional Setting
must be set correctly according to the actual mains grid.
Parameter 14-52 Fan Control
Table 744: Parameter 14-52 Fan Control
14-52 Fan Control
Default value: [0] Auto
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Select the minimum speed of the main fan.
Op-
tion
Name
Description
[0]*
Auto
Select
[0] Auto
to run fan only when internal temperature in the drive is in the range 35 °C (95 °F) to ap-
proximately 55 °C (131 °F). The fan runs at low speed below 35 °C (95 °F), and at full speed at approxi-
mately 55 °C (131 °F).
[1]
On 50%
The fan always runs at 50% speed or above. The fan runs at 50% speed at 35 °C (95 °F), and at full speed at
approximately 55 °C (131 °F).
[2]
On 75%
The fan always runs at 75% speed or above. The fan runs at 75% speed at 35 °C (95 °F), and at full speed at
approximately 55 °C (131 °F).
[3]
On 100%
The fan always runs at 100% speed.
[4]
Auto (Low
temp env.)
This option is the same as
[0] Auto
, but with special considerations around and below 0 °C (32 °F). In op-
tion
[0] Auto
there is a risk that the fan starts running around 0 °C as the drive detects a sensor fault and
thus protects the drive while reporting
warning 66, Heat sink Temperature Low
. Option
[4] Auto (Low temp
env.)
can be used in very cold environments and prevents the negative effects of this further cooling and
avoids
warning 66, Heat sink Temperature Low
.
Parameter 14-53 Fan Monitor
Table 745: Parameter 14-53 Fan Monitor
14-53 Fan Monitor
Default value: [1] Warning
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Select the drive action if a fan fault is detected.
Option
Name
Description
[0]
Disabled
[1]*
Warning
[2]
Trip
AU275636650261en-000101 / 130R0334 | 469
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide