Parameter 0-42 [Auto On] Key on LCP
Table 30: Parameter 0-42 [Auto On] Key on LCP
0-42 [Auto On] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option Name
Description
[0]
Disabled
Avoids accidental stop of the drive in auto-on mode.
[1]*
Enabled
[2]
Password Avoids unauthorized start in auto-on mode. If
parameter 0-42 [Auto on] Key on LCP
is included in the Quick
Menu, then define the password in
parameter 0-65 Personal Menu Password
.
Parameter 0-43 [Reset] Key on LCP
Table 31: Parameter 0-43 [Reset] Key on LCP
0-43 [Reset] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option Name
Description
[0]
Disabled
No effect when [Reset] is pressed. Avoids accidental alarm reset.
[1]
Enabled
[2]
Password
Avoids unauthorized start in auto-on mode. If
parameter 0-43 [Reset] Key on LCP
is included in
the Quick Menu, then define the password in
parameter 0-65 Personal Menu Password
.
[7]
Enabled without OFF
Resets the drive without setting it in Off mode.
[8]
Password without
OFF
Resets the drive without setting it in Off mode. A password is required when pressing [Reset]
(see option
[2] Password
).
Parameter 0-44 [Off/Reset] Key on LCP
Table 32: Parameter 0-44 [Off/Reset] Key on LCP
0-44 [Off/Reset] Key on LCP
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Enable or disable the [Off/Reset] key.
Option
Name
Description
[0]
Disabled
[1]*
Enabled
[2]
Password
AU275636650261en-000101 / 130R0334 | 55
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide