Parameter 36-22 Terminal X49/3 High Voltage
Table 1318: Parameter 36-22 Terminal X49/3 High Voltage
36-22 Terminal X49/3 High Voltage
Default value: 10 V
Parameter type: Range, 0 - 10 V
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Parameter 36-23 Terminal X49/3 High Current
Table 1319: Parameter 36-23 Terminal X49/3 High Current
36-23 Terminal X49/3 High Current
Default value: 20 mA
Parameter type: Range, 0 - 20 mA
Setup: All setups
Conversion index: -3
Data type: Int16
Change during operation: True
Parameter 36-24 Terminal X49/3 Low Ref./Feedb. Value
Table 1320: Parameter 36-24 Terminal X49/3 Low Ref./Feedb. Value
36-24 Terminal X49/3 Low Ref./Feedb. Value
Default value: 0 ReferenceFeedbackUnit Parameter type: Range, -999999.999 - 999999.999
ReferenceFeedbackUnit
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
Parameter Parameter 36-25 Terminal X49/3 High Ref./Feedb. Value
Table 1321: Parameter 36-25 Terminal X49/3 High Ref./Feedb. Value
36-25 Terminal X49/3 High Ref./Feedb. Value
Default value: 100 ReferenceFeedbackU-
nit
Parameter type: Range, -999999.999 - 999999.999
ReferenceFeedbackUnit
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
Parameter 36-26 Term. X49/3 Filter Time Constant
Table 1322: Parameter 36-26 Term. X49/3 Filter Time Constant
36-26 Term. X49/3 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X49/3. A high time constant value improves dampening but also increases the time delay through the filter.
5.29.4 36-3* Analog Input X49/5