Number Description
Warning Alarm/trip Alarm/trip
lock
Parameter reference
38
Internal fault
–
X
X
–
39
Heat sink sensor
–
X
X
–
40
Overload of digital output termi-
nal 27
(X)
–
–
Parameter 5-00 Digital I/O Mode
,
parame-
ter 5-01 Terminal 27 Mode
41
Overload of digital output termi-
nal 29
(X)
–
–
Parameter 5-00 Digital I/O Mode
,
parame-
ter 5-02 Terminal 29 Mode
42
Ovrld X30/6-7
(X)
–
–
–
43
Ext. supply (option)
X
–
–
–
45
Ground fault 2
–
X
(1)
X
Parameter 14-90.5 Fault Level
46
Pwr. card supply
–
X
X
–
47
24 V supply low
X
X
X
–
48
1.8 V supply low
–
X
X
–
50
AMA calibration failed
–
X
–
–
51
AMA check U
nom
and I
nom
–
X
–
–
52
AMA low I
nom
–
X
–
–
53
AMA motor too big
–
X
–
–
54
AMA motor too small
–
X
–
–
55
AMA parameter out of range
–
X
–
–
56
AMA interrupted by user
–
X
–
–
57
AMA time-out
–
X
–
–
58
AMA internal fault
X
X
–
–
59
Current limit
X
X
–
Parameter 14-24 Trip Delay at Current
Limit
60
External interlock
X
X
–
–
61
Feedback error
(X)
(X)
–
Parameter 4-30 Motor Feedback Loss
Function
62
Output frequency at maximum
limit
X
X
–
–
63
Mechanical brake low
–
(X)
–
Parameter 4-30 Motor Feedback Loss
Function
64
Voltage limit
X
–
–
–
65
Control board overtemperature
–
X
X
Parameter 14-90.11 Fault Level
66
Heat sink temperature low
X
–
–
–
67
Option configuration has changed
–
X
–
–
68
Safe stop
(X)
(X)
(1)
–
Parameter 5-19 Terminal 37 Safe Stop
AU275636650261en-000101 / 130R0334 | 693
Danfoss A/S © 2022.12
Troubleshooting
VLT AutomationDrive FC 301/302
Programming Guide
Summary of Contents for VLT AutomationDrive FC 301