Illustration 63: On Delay, Relay
Parameter 5-42 Off Delay, Relay
Table 363: Parameter 5-42 Off Delay, Relay
5-42 Off Delay, Relay
Default value: 0.01 s
Parameter type: Range, 0.01 – 600 s, Array [9]
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
Enter the delay of the relay cutout time. Select 1 of 2 internal mechanical relays in an array function. See
parameter 5-40 Function
Relay
for details. If the selected event condition changes before a delay timer expires, the relay output is unaffected.
Selected
event
Relay
output
On delay
P 5-41
Off delay
P 5-42
e3
0b
a1
72
.1
1
Illustration 64: Off Delay, Relay
5.6.5 5-5* Pulse Input
N O T I C E
The following parameters are only available in FC 302:
Parameter 5-50 Term. 29 Low Frequency
Parameter 5-51 Term. 29 High Frequency
Parameter 5-52 Term. 29 Low Ref./Feedb. Value
Parameter 5-53 Term. 29 High Ref./Feedb. Value
Parameter 5-54 Pulse Filter Time Constant #29
The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and
filter settings for the pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (
parameter 5-13 Termi-
nal 29 Digital Input
) or terminal 33 (
parameter 5-15 Terminal 33 Digital Input
) to
[32] Pulse input
. If terminal 29 is used as an input, set
parameter 5-01 Terminal 27 Mode
to
[0] Input
.
AU275636650261en-000101 / 130R0334 | 217