Option
Name
Description
[6]
Transaction failed
[7]
SO config check
[8]
SO config check done
Parameter 8-47 BTM Timeout
Table 524: Parameter 8-47 BTM Timeout
8-47 BTM Timeout
Default value: 60 s
Parameter type: Range, 1 - 360 s
Setup: 1 setup
Conversion index: 0
Data type: Uint16
Change during operation: False
Select the BTM timeout after a BTM transaction has been started. Timeout is between each acyclic write of parameters.
Parameter 8-48 BTM Maximum Errors
Table 525: Parameter 8-48 BTM Maximum Errors
8-48 BTM Maximum Errors
Default value: 21
Parameter type: Range, 0 - 21
Setup: 1 setup
Conversion index: 0
Data type: Uint8
Change during operation: True
Select the maximum allowed number of bulk transfer mode errors before aborting. If it is set to maximum, there is no abort.
Parameter 8-49 BTM Error Log
Table 526: Parameter 8-49 BTM Error Log
8-49 BTM Error Log
Default value: Size related
Parameter type: Range, 0.000 - 9999.255, Array [22]
Setup: 1 setup
Conversion index: -3
Data type: Uint32
Change during operation: True
List of parameters that failed during bulk transfer mode. The value after the decimal break is the fault code (255 stands for no error).
5.9.6 8-5* Digital/Bus
Parameters for configuring the control word merging.
N O T I C E
These parameters are only active when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Parameter 8-50 Coasting Select
Table 527: Parameter 8-50 Coasting Select
8-50 Coasting Select
Default value: [3] Logic OR
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the trigger for the coasting function.
AU275636650261en-000101 / 130R0334