Guarantees a minimum off-time for the capacitors. The timer starts once the AHF capacitor disconnects and has to expire before the
output is allowed to be on again. It only turns on again if the drive power is 20–30%.
5.6.9 5-9* Bus-controlled
N O T I C E
The following parameters are only available in FC 302:
Parameter 5-95 Pulse Out #29 Bus Control
Parameter 5-96 Pulse Out #29 Timeout Preset
This parameter group selects digital and relay outputs via a fieldbus setting.
Parameter 5-90 Digital & Relay Bus Control
Table 389: Parameter 5-90 Digital & Relay Bus Control
5-90 Digital & Relay Bus Control
Default value: 0
Parameter type: Range, 0 - 0xFFFFFFFF
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
This parameter holds the state of the digital outputs and relays that is controlled by bus. A logical 1 indicates that the output is high
or active. A logical 0 indicates that the output is low or inactive.
Table 390: Bus-controlled Digital Outputs and Relays
Bit
Output/Relay
0
Digital output terminal 27
1
Digital output terminal 29
2
Digital output terminal X30/6
3
Digital output terminal X30/7
4
Relay 1 output terminal
5
Relay 2 output terminal
6
Option B relay 1 output terminal
7
Option B relay 2 output terminal
8
Option B relay 3 output terminal
9-15
Reserved for future terminals
16
Option C relay 1 output terminal
17
Option C relay 2 output terminal
18
Option C relay 3 output terminal
19
Option C relay 4 output terminal
20
Option C realy 5 output terminal
21
Option C relay 6 output terminal
AU275636650261en-000101 / 130R0334 | 229
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide