Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X49/5. A high time constant value improves dampening but also increases the time delay through the filter.
5.29.5 36-4* Output X49/7
N O T I C E
The following parameter is only available in FC 302:
Parameter 36-41 Terminal X49/7 Digital Output
Use the parameters in this group to configure the mode of inputs and outputs of VLT® Programmable I/O MCB 115.
Parameter 36-40 Terminal X49/7 Analogue Output
Table 1330: Parameter 36-40 Terminal X49/7 Analogue Output
36-40 Terminal X49/7 Analogue Output
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the functionality of terminal X49/7.
Option Name
Description
[0]*
No operation
Indicates no signal on the analog output.
[52]
MCO
[100]
Output frequency
0 Hz = 0 mA; 100 Hz = 20 mA.
[101]
Reference
Parameter 3-00 Reference Range [Min - Max]
0% = 0 mA; 100% = 20 mA
Parameter 3-00 Reference Range [-Max - Max]
-100% = 0 mA; 0% = 10 mA; +100% = 20 mA.
[102]
Feedback
[103]
Motor current
The value is taken from
parameter 16-37 Inv. Max. Current
. The inverter maximum current (160%
current) is equal to 20 mA.
Example:
Inverter normal current (11 kW) is 24 A. 160 %=38.4 A. Motor normal current is 22 A, the
readout is 11.46 mA.
20 mA × 22
A
38 . 4
A
= 11 . 46 mA
When the normal motor current is equal to 20 mA, the output setting of
parameter 6-52 Terminal
42 Output Max Scale
is:
I
VLT, MAX
× 100
I
Motor, Nom
= 38 . 4 × 100
22
= 175 %
[104]
Torque rel to limit
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
.
[105]
Torque relate to
rated
The torque is related to the motor torque setting.
[106]
Power
Taken from
parameter 1-20 Motor Power [kW]
.
[107]
Speed
Taken from
parameter 3-03 Maximum Reference
. 20 mA equals the value in
parameter 3-03 Maxi-
mum Reference
.
[108]
Torque
Torque reference related to 160% torque.
[109]
Max out freq
0 Hz = 0 mA,
parameter 4-19 Max Output Frequency
= 20 mA.
AU275636650261en-000101 / 130R0334 | 643
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide