M-6280A Digital Capacitor Bank Control
*Only available with VAr and Current Control Mode option.
– Number of Occurrences – Selecting the Number of Occurrences calculates the End Date and
displays it.
– Start Time
– End Time – Selecting the End Time Calculates the Duration and displays it rounded to the
nearest tenth of a minute.
– Duration – Selecting Duration calculates the End Time and displays it rounded to the nearest
tenth of a minute.
– Recurrence Pattern – Provides a choice between Daily and Weekly.
•
Above and Below Temperature Profile Trigger
– The Above and Below Temperature Triggers provide
the user with the ability to set a temperature between -40° and 185° F, or -40° and 85° C that will
trigger a Settings Profile change when exceeded.
•
Reverse Power Profile Trigger
– The Reverse Power trigger does can be selected to "No Bias",
"Forward Bias" or "Reverse Bias". When Reverse Power is sensed, the selected Settings Profile will
be switched to.
Additional Settings
VT/CT Setup:
– Voltage Multiplier:
Adjustable from 0.1 to 3260.0 in 0.1 increments
– VT Correction:
Adjustable from -15.0 V to +15.0 V in 0.1 V increments
– Phase Current Multiplier*:
Adjustable from 1.0 to 200 in .01 increments
– Neutral Current Multiplier:
5 A Neutral CT and Line Post Sensor – Adjustable from 1.0 to 150 in 0.1 increments
200 mA Neutral CT – Adjustable from 1.0 to 3260 in 0.1 increments
Counters:
– Resettable Counter:
A software counter that increments by one count per Close or
Open operation. Resettable to 0.
– Operation Counter Preset:
A software counter which increments by one count per Close Only or,
Open or Close operation. Presettable from 0 to 999,999.
– Resettable Counter Alarm Limit:
A limit that alerts the user either by communications and/or a
programmable alarm. It is settable from 0 to 999,999.
– Daily Operation Counter Limit:
A limit that will block any further Close/Open operation until
12:00 AM and alerts the user either by communications and/or a programmable alarm. It is settable
from 2 to 99 and can be enabled or disabled in "Remote" and/or "Manual" Mode. This counter is
always enabled in "Auto" Mode.
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...