M-6280A Instruction Book
4–58
4.2
System Setup
USER PROGRAMMABLE ALARM RELAY
The User Programmable Alarm Relay is a
non-latching relay that is capable of switching 6
A at 125 VAC or 0.2 A at 125 V dc and is user-
programmable to indicate one or more of the
following conditions:
• Maximum Voltage Limit
• Minimum Voltage Limit
• Remote Overvoltage Limit
• Remote Undervoltage Limit
• Bank/Switch Failed Level 2
• Bank/Switch Failed Level 1
• Resettable Counter Limit
• Daily Operation Counter Limit
• Remote Manual
• Self Test
• Voltage Harmonics
• Current Harmonics
• Voltage THD Lockout
• Current THD Lockout
• Delta Voltage (cannot be deselected)
The Alarm Relay will de-energize and generate an
output without any of the conditions being enabled
when power to the unit is lost.
Prog Alarm Function
11111111111111
Prog Alarm Function
00000000000000
All Disabled
(factory Setting)
All Enabled
Maximum Voltage Limit
(exceeded)
Minimum Voltage Limit
(exceeded)
Remote Overvoltage Limit
(exceeded)
Remote Undervoltage Limit
(exceeded)
Bank/Switch Failed Level 2
(true)
Resettable Operation Counter
(exceeded)
Bank/Switch Failed Level 1
(true)
Remote Manual
(in effect)
Self Test
(failure)
Voltage Harmonics
(exceeded)
Current Harmonics
(exceeded)
Press ENT to enter change mode
Prog Alarm Function
00000000000000
UTIL
ENT
UTIL
ENT
max. volt limit
00000000000000 C
SETP
CNFG
max. volt limit
00000000000001 C
MNTR
min. volt limit
00000000000001 C
CNFG
Programmable Alarm
Flashing "Underline" and
"C" indicates change mode
0 disables alarm condition
1 enables alarm condition
Alarm condition displayed on top
line is based on the digit that is
undelined on the bottom line
Use UP or DOWN to select 0 or 1
Use LEFT or RIGHT to navigate to
desired Alarm Condition
Press ENT to exit change
mode and save settings
Daily Operation Counter Limit
(exceeded)
Voltage THD Lockout
(in effect)
Current THD Lockout
(in effect)
Figure 4-39
Programmable Alarm Function Programming
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...