M-6280A Instruction Book
4–112
10.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed. Go to Step 13.
Time Delay
XXXX
Sec
C
11.
If Level Access is active, then the Level
Access prompt will be displayed.
ENTER LEVEL ACCESS
_
NOTE
: When entering the Level Access Code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
12.
Enter a valid Level Access Code, then
press the
"ENT"
pushbutton.
If a valid Level Access Code was
entered, then the display will briefly flash
a confirmation screen and then display
the following:
Time Delay
XXXX
Sec
C
If not, re-enter a valid code.
13.
Utilizing the arrow pushbuttons enter
the desired Phase Overcurrent Time
Delay (1 to 8160 seconds in 1 second
increments), then press the "ENT"
pushbutton. The following will be
displayed reflecting the Phase OC Time
Delay that was entered.
Time Delay
XXXX Sec
Setting Phase Overcurrent From CapTalk
1. Select
Setup/Phase Overcurrent from
the CapTalk toolbar. CapTalk will display
the Phase Overcurrent dialog screen
(Figure 4-51).
2.
Enter the desired Phase Overcurrent
Pickup setting (10 to 2000 A in 1 A
increments.
3.
Enter the desired Phase Overcurrent
Time Delay setting (1 to 8160 Sec in 1
Sec increments).
4.
Select "Save". CapTalk will display a
"Confirm Writing to Device" confirmation
screen (Figure 4-2).
5.
Select "OK". CapTalk will display a
"Setpoints Successfully Written to
Control" confirmation screen (Figure
4-14).
The Phase Overcurrent feature must
be selected as a triggering event in the
Oscillograph Recorder in order to trigger
the Oscillograph Recorder.
Figure 4-51 Phase Overcurrent Settings
Dialog Screen
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...