M-6280A Instruction Book
4–44
Optional RS-232 Module Setup From The HMI
This procedure provides the steps necessary
to setup all
RS-232 Port Module parameters.
Parameter definitions and the default value [default
value] for each parameter are included below:
• Comm Protocol – Allows selection
between standard protocols, DNP 3.0 or
Modbus. [MODBUS
®
]
• Baud Rate – Selects baud rate for COM2,
located on the top of the control. [115,200]
• Parity – None, odd or even parity is
available. [NONE]
• Stop Bits – One or two stop bits are
available. [TWO STOPBITs]
• Sync Time – This time delay improves
robust operation when communication
lines are intermittent. Communication
dead-sync time is the time that the control
will wait from the last received character
and continue without attempting to
resynchronize. [50 ms]
• TX Delay – 1 to 5000 ms in 1 ms
increments. [10 ms]
If the default value for a parameter does not need to
be changed, then skip the applicable steps.
1.
Ensure the control is energized.
NOTE
: If Access Code protection has been
implemented on the control, a valid Level
2 Access Code is required to be entered
to manually configure each element of
the RS-232 port.
2.
Press the Right Arrow (COMM Hot
Button) pushbutton to awaken the
unit. The menu will advance to either
"COMMUNICATION" or if a Memory
Card is present in the Smart Flash SD
CARD slot "Memory Card".
COMMUNICATION
CNFG
UTIL
OR
Memory Card
3.
If the "Communication" menu is
displayed, then press the Down Arrow
pushbutton once. The unit will display
the following:
Comm Settings
4.
From either the "Comm Settings" or
"Memory Card" menu, press the Right
or Left Arrow pushbutton as necessary
until "RS232" is displayed.
RS232
5.
Press the Down arrow pushbutton once.
The unit will display the following:
Protocol
MODBUS
6.
Press the "ENT" pushbutton. If Level
2 Access is not active or has been
previously input, the following will be
displayed. Go to Step 9.
Protocol
MODBUS C
7.
If Level 2 Access is active, the Level 2
Access prompt will be displayed.
ENTER LEVEL 2 ACCESS
_
NOTE
: When entering the Level 2 Access code,
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
8.
Enter a valid Level 2 Access code, then
press the "ENT" pushbutton.
If a valid Level 2 Access code was
entered, the display will briefly flash a
confirmation screen and display the
following:
Protocol
MODBUS C
If not, re-enter a valid code.
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...