Configuration – 4
4–111
Phase Overcurrent
The Phase Overcurrent feature measures individual
phase currents. Any phase current that exceeds the
pickup level (10 to 2000 Amps) will cause the control
to start a Time Delay timer (1 to 8160 Cycles).
When the Time Delay expires the control issues
an Overcurrent Phase A (B, C) event. If at any time
during Time Delay timing the phase current value
decreases to less than the pickup level, the Time
Delay will reset. The control keeps track of which
individual phase caused the event to happen.
NOTE
: When the Phase Overcurrent function
is enabled, if the Sequence of Events
(SOE) recorder is not enabled a dialog
screen will be displayed prompting the
user to enable SOE and to choose the
Phase Overcurrent trigger.
Setting Phase Overcurrent From The HMI
To set the Phase Overcurrent feature from the HMI
proceed as follows:
1.
Press the Down Arrow (CNFG Hot Button)
pushbutton to awaken the unit. The menu
will advance to "CONFIGURATION".
CONFIGURATION
SETP
COMM
2.
Press the Down Arrow pushbutton once.
The unit will display the following:
Cap Settings
3.
Press the Right or Left Arrow
pushbuttons as necessary until the
"Phase Overcurrent" screen is displayed.
Phase Overcurrent
4.
Press the Down Arrow as necessary until
the "Pickup" screen is displayed.
Pickup
XXXX A
5.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed. Go to Step 8.
Pickup
XXXX
A C
6.
If Level Access is active, then the Level
Access prompt will be displayed.
ENTER LEVEL ACCESS
_
NOTE
: When entering the Level Access Code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
7.
Enter a valid Level Access Code, then
press the
"ENT"
pushbutton.
If a valid Level Access Code was
entered, then the display will briefly flash
a confirmation screen and then display
the following:
Pickup
XXXX
A C
If not, re-enter a valid code.
8.
Utilizing the Up/Down Arrow pushbuttons
enter the desired Phase Overcurrent
setting "10 to 2000 Amps in one amp
increments", then press the
"ENT"
pushbutton. The following will be
displayed reflecting the Phase
Overcurrent setting that was entered.
Pickup
XXXX A
9.
Press the Down Arrow as necessary until
the "Time Delay" screen is displayed.
Time Delay
XXXX Sec
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...