M-6280A Instruction Book
4–100
NOTE
: From this point on in this procedure it
is assumed that a valid Access Level
1 Code has been previously entered. If
not, a valid Level 1 Access Code will be
required to be entered as described in
Step 7.
10.
Press the Down Arrow as necessary
until the "Level2 Current Lmt" screen is
displayed.
Level2 Current Lmt
2.0 A
11.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed.
Level2 Current Lmt
2.0 A
C
12.
Utilizing the arrow pushbuttons enter
the desired Bank Failed Level 2 current
limit (1.0 to 200.0 A in .01 increments),
then press the
"ENT" pushbutton. The
following will be displayed reflecting the
Bank Failed Level 2 Current Limit that
was selected.
Level2 Current Lmt
XXX.X A
13.
Press the Down Arrow as necessary until
the "Bank Failed Time Delay" screen is
displayed.
Bank Failed Delay
60 Sec
14.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed.
Bank Failed Delay
60 Sec
C
15.
Utilizing the arrow pushbuttons enter
the desired Bank Failed Delay (10 to
300 seconds in 1 second increments),
then press the
"ENT" pushbutton. The
following will be displayed reflecting
the Bank Failed Time Delay that was
selected.
Bank Failed Delay
XXX.X Sec
NOTE
: The "Prior Operation Action" element of
the Bank/Switch Failed Level 2 feature
implements a user selected set of control
actions, when enabled. Prior Operation
is determined by the control to be when
neutral current is detected within 60
seconds of capacitor bank operation.
16.
Press the Down Arrow as necessary
until the "Prior Operation Action" screen
is displayed.
Prior OP Action
000
17.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed.
Prior OP Action
000
C
NOTE
: The cursor will be positioned under the
right hand zero which corresponds to
"Retry Operation". The center cursor
position corresponds to "Reverse
Operation and Block" and the left hand
cursor position corresponds to "Rest
Block".
18.
Utilizing the Up/Down Arrow pushbuttons
enter a "1" for those actions to be taken
and a "0" for those that are to be disabled,
then press the
"ENT" pushbutton. The
following will be displayed reflecting the
selections that were made.
Prior OP Action
XXX
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...