2–10
M-6280A Instruction Book
As long as the control is powered via the Backup
DC input, none of the three positions of this switch
have any affect on communications to a control or to
any other device in the same communications loop
with it. If backup power is not supplied to the control,
then placing the switch in "EXT" without a source
applied to the front panel meter jacks or in "OFF"
will result in the control being de-energized. While
de-energized, the control will not respond to any
communications via fiber. If a serial fiber loop is used
to connect multiple devices to one communication
port, any other device in the serial loop will not be
able to communicate either.
With the Voltage Source switch in "EXT" with no
AC input voltage applied or in "OFF", Primary and
Secondary parameters that use secondary voltage
as a component will not read correctly as there
is no AC sensing voltage applied. This includes
Load Voltage, Source Voltage, Meter Out Voltage,
Normalizing Voltage, Primary Voltage, Primary
Watts, Primary VAr's, etc.
Binding Posts
■
NOTE: The Binding Posts are rated for a
maximum power input of 140 V ac, 8 VA.
8
WARNING: Operating personnel MUST NOT
connect uninsulated test connections to the
binding post as they can create a shock hazard.
EXTERNAL POWER binding posts allow application
of a 120 V RMS nominal voltage to the unit for test
procedures.
8
WARNING: A shock hazard exists due to the
presence of voltage on the Meter Out Binding
Posts.
METER OUT binding posts allow reading of the
input voltage.
Smart Flash SD Card Slot
The Smart Flash SD Card Slot allows the user to:
•
Quick Capture
•
Load and Save Setpoints
•
Save Datalog files
•
Save Sequence of Events files
•
Save Oscillograph records
•
Clone Save and Load
•
Load and Save DNP files
•
Save Metering Data
•
Update Firmware
•
SD Card User Access Code
•
Save Wake Screen Data
The steps necessary to perform these actions are
described later in this chapter.
Fuses
▲
CAUTION: Failure to utilize proper replacement
fuses will result in damage to the control.
The Digital Capacitor Bank Control back panel
provides access to three U
L
®
recognized replaceable
fuses.
• Test – 3 A, 250 V ac, 3 AG
BECO Part No. 420-00826
• Switch Power – 12 A, 250 V ac, 3 AG
BECO Part No. 420-00871
• Voltage – 0.5 A, 250 V ac, 3 AG
BECO Part No. 420-00832
• Line Post Sensor – 0.125 A, 250 V ac, 8 AG
BECO Part No. 420-00926
Replace using proper type voltage and current
rating.
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...