Configuration – 4
4–105
NOTE
: When entering the Level Access Code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
7.
Enter a valid Level Access Code, then
press the
"ENT"
pushbutton.
If a valid Level Access Code was
entered, then the display will briefly flash
a confirmation screen and then display
the following:
Bank Status
ENABLE C
If not, re-enter a valid code.
8.
Utilizing the Up/Down Arrow pushbuttons
select either "Enable" or "Disable"
Bank Status limits, then press the
"ENT" pushbutton. The following will be
displayed reflecting the selection that
was made.
Bank Status
(ENABLE or disable)
9. Based on the selection made in
Step 8, proceed as follows to complete
the Bank Status limits setup:
• If Bank Status limits was "Enabled",
then proceed to Step 10.
• If Bank Status was "Disabled", no
further action is required.
10.
Press the Down Arrow as necessary
until the "Bank Status Closed" screen
is displayed.
Bank Status Closed
0.20 A
11.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed. Go to Step 14.
Bank Status Closed
0.20
A C
12.
If Level Access is active, then the Level
Access prompt will be displayed.
ENTER LEVEL ACCESS
_
NOTE
: When entering the Level Access Code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
13.
Enter a valid Level Access Code, then
press the
"ENT"
pushbutton.
If a valid Level Access Code was
entered, then the display will briefly flash
a confirmation screen and then display
the following:
Bank Status Closed
0.20
A C
If not, re-enter a valid code.
14.
Utilizing the arrow pushbuttons enter
the desired Bank Status Closed current
limit (0.10 to 10.0 A in .01 increments),
then press the
"ENT" pushbutton. The
following will be displayed reflecting the
Bank Status Closed current limit that
was selected.
Bank Status Closed
X.XX A
15.
Press the Down Arrow as necessary
until the "Bank Status Open" screen is
displayed.
Bank Status Open
0.10 A
16.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed. Go to Step 19.
Bank Status Open
0.10
A C
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...