3–42
M‑6280A Instruction Book
Number of
Partitions
Cycles Per Partition
Without Phase Current
Cycles Per Partition
With Phase Current
1
2730
2048
2
1820
1365
3
1365
1024
4
1092
819
5
910
682
6
780
585
7
682
512
8
606
455
9
546
409
10
496
372
11
455
341
12
420
315
13
390
292
14
364
273
15
341
256
16
321
240
Table 3‑1 Example Oscillograph Recorder Partitions and Cycles for 16 Samples/Cycle
Setup/Oscillograph/Setup
The
Oscillograph Recorder provides comprehensive
data recording (voltage, current and status input/
output signals) for all monitored waveforms (at 16,
32 or 64 samples per cycle). Oscillograph data can
be downloaded using the communications ports
to any Windows
™
based computer running the
CapTalk
®
S-6280 Communications Software. Once
downloaded, the waveform data can be examined
and printed using CapPlot.
The general information required to setup the
Oscillograph Recorder (Figure 3‑54) includes:
•
Number of Par titions – When
untriggered, the recorder continuously
records waveform data, keeping the
data in a buffer memory. The recorder’s
memory may be partitioned into 1 to 16
partitions (Table 3‑1). See Chapter 4 for
32 and 64 Samples/Cycle.
When triggered, the time stamp is
recorded and the recorder continues
recording for a user-defined period. The
snapshot of the waveform is stored in
memory for later retrieval using CapTalk
S-6280 Communications Software.
•
Samples/Cycle – The number of samples/
cycle can be selected to either 16, 32 or
64 samples/cycle.
•
Post-Trigger Delay – A post-trigger delay
of 5% to 95% must be specified. After
triggering, the recorder will continue to
store data for the programmed portion
of the total record before rearming for
the next record. For example, a setting
of 80% will result in a record with 20%
pre-trigger data and 80% post-trigger data.
Figure 3‑54 Oscillograph Setup Dialog Screen
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...