Configuration – 4
4–101
NOTE:
The following sequence of steps
assumes that all "Prior Operation
Actions" have been enabled.
19.
Press the Down Arrow as necessary until
the "Number of Retry Attempts" screen
is displayed.
No of Retry Attempts
1
20.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed.
No of Retry Attempts
1
C
21.
Utilizing the arrow pushbuttons enter the
desired Number of Retry Attempts (1 to
9), then press the "ENT"
pushbutton.
The following will be displayed reflecting
the Number of Retry Attempts that were
selected.
No of Retry Attempts
X
22.
Press the Down Arrow as necessary until
the "Block Reset Time Delay" screen is
displayed.
Block RST Time Delay
24 Hrs
23.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed.
Block RST Time Delay
24
Hrs
C
24.
Utilizing the arrow pushbuttons enter the
desired Block Reset Time Delay (1 to 72
hours), then press the "ENT"
pushbutton.
The following will be displayed reflecting
the Block Reset Time Delay that was
entered.
Block RST Time Delay
XX Hrs
NOTE
: The "No Prior Operation" element of
the Bank/Switch Failed Level 2 feature
implements a user selected set of
control actions, when enabled. No Prior
Operation is determined by the control
to be when neutral current is detected
greater than 60 seconds after capacitor
bank operation.
25.
Press the Down Arrow as necessary until
the "No Prior Operation Enable/Disable"
screen is displayed.
No Prior OP En/Dis
ENABLE
26.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed.
No Prior OP En/Dis
ENABLE C
27.
Utilizing the Up/Down Arrow pushbuttons
select either "Enable" or "Disable"
No Prior Operation, then press the
"ENT" pushbutton. The following will be
displayed reflecting the selection that
was made.
No Prior OP En/Dis
(ENABLE or disable)
28.
Based on the selection made in Step 27,
proceed as follows to complete the No
Prior Operation setup:
• If No Prior Operation was "Enabled",
then proceed to Step 29.
• If No Prior Operation was "Disabled",
no further action is required.
29.
Press the Down Arrow as necessary until
the "Open Lockout Time Delay" screen
is displayed.
Open Lockout T Delay
120 Minutes
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...