A–28
M-6280A Instruction Book
Communication/Ethernet (Cont.'d)
Auto Negotiation
ENABLE
When enabled allows the user to set the Ethernet
Port to a fixed speed of 100 mbps.
Keepalive Time
120 sec
Allows the Keepalive Time to be set to a value from
1 to 50000 seconds.
If no communication activity is detected on a
previously open ethernet socket, for the amount
of time specified by the "Keepalive time" setting,
the control will then close the socket and make it
available for future connection.
NOTE Keepalive time applies only to Ethernet
communication.
Communication/Bluetooth
Bluetooth Enable
ENABLE
Enables or disables the Bluetooth
®
feature when
installed on the control.
Reset
Ready Press ENTER
Allows the user to reset the Bluetooth Module to
"Beckwith" factory default settings.
Protocol
MODBUS
Provides the ability to select either MODBUS or
DNP3.0 protocol.
Authentication
disable
Enables or disables Authentication and provides
the means to enter a Pass Key when set (1 to 16
characters).
Friendly Name
M6280A
Allows the user to name the unit (maximum of 32
characters).
Bluetooth Pass Reset
Ready Press ENTER
This feature allows the Bluetooth Authentication
setting to be set to "Disable". This action results in
the Bluetooth Passkey being reset.
Control BT Device
xx:xx:xx:xx:xx:xx
Displays Bluetooth device address of the Bluetooth
module.
Bluetooth Mode
Mode0
Provides the user with capability to select either
Bluetooth Mode0 or Mode1.
Communication/RS232
Protocol
MODBUS
Allows selection between standard protocols,
DNP3.0 or MODBUS
®
.
Baud Rate
115200
Selects Baud Rate for the RS232 port.
Figure A‑9 Communication Screens (page 4 of 6)
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...