3–9
CapTalk – 3
3.8
Communications with Multiple
Controls
CAUTION: Each control connected to either a
direct or modem connection configuration must
have a unique communications address. If two or
more controls share the same address, corrupted
communication will result.
The remote addressing capability of CapTalk
®
S-6280 Communications Software and the M-6280A
Digital Capacitor Bank Control allows multiple
controls to share a direct or network connection. A
fiber optic loop network (see Figure 3‑7, Fiber Optic
Connection Loop), RS‑485 tree configuration (see
Figure 3‑8, RS‑485 Connection Tree) or Ethernet
Network (see Figure 3‑9, Optional Ethernet Network
Connection) may also be used.
A control address of zero is a "wild card" that will
illicit a response from all controls on a shared
connection and result in corrupted communication.
With these arrangements, any control can be
selected from within CapTalk by specifying it’s
unique communications address, ranging from 1
to 200. The communication address must have
previously been set from the control’s front panel.
3.9 Cautions
Control and CapTalk Compatibility
Every attempt has been made to maintain
compatibility with previous control software
versions. In some cases (most notably, with older
controls), compatibility cannot be maintained.
However, CapTalk should work correctly with more
than one version of the M-6280A Series Digital
Capacitor Bank Controls on a single bus, provided
that the controls are all set to use the same protocol.
If there is any question about compatibility, contact
the factory.
Control Priority
Control conflicts will not occur as local commands
initiated from the front panel receive priority
recognition.
Time and Date Stamping
Time and date stamping of events is only as useful
as the validity of the control’s internal clock. Under
the
Configuration/System Clock menu, the Set
Control Date/Time command allows you to manually
set the control’s clock. For reference, the computer’s
clock is also displayed.
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...