M-6280A Instruction Book
4–138
33. Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed. Go to Step 36.
Open Inverse Time
1800
Sec
C
34.
If Level Access is active, then the Level
Access prompt will be displayed.
ENTER LEVEL ACCESS
_
NOTE: When entering the Level Access Code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
35.
Enter a valid Level Access Code, then
press the "ENT" pushbutton.
If a valid Level Access Code was
entered, then the display will briefly flash
a confirmation screen and then display
the following:
Open Inverse Time
1800
Sec
C
If not, re‑enter a valid code.
36.
Utilizing the arrow pushbuttons enter the
desired Open Inverse Time (0 to 3600),
then press the "ENT" pushbutton. The
following will be displayed reflecting the
Open Inverse Time that was selected.
Open Inverse Time
XXXX
Sec
Selecting Auto Adaptive Auto Control Mode
and Setting Auto Adaptive Auto Control Mode
Limits From CapTalk
®
To enter Auto Adaptive Auto Control Mode Limits
Settings from CapTalk proceed as follows:
1. Select
Setup/Setpoints from the
CapTalk toolbar. CapTalk will display the
Setpoints dialog screen (Figure 4‑60).
2.
Verify that the correct Setpoint Profile is
selected for editing.
3.
From the Auto Control Mode section of
the dialog screen select "Enable Voltage
Control" and "Auto Adaptive". Figure
4‑61 will display.
4.
From the Auto Control Mode section of
setpoints the dialog screen select either
"Fixed" or "Average" for Bandcenter.
5.
If Average was selected in Step 4, then
go to Step 8.
6. From the Auto Control Mode section
of the dialog screen enter the desired
"Bandcenter" setting (100.0 to 135.0).
7. From the Auto Control Mode section
of the dialog screen enter the desired
"Bandwidth Multiplier" (1.0 to 2.0)
setting.
8. From the Auto Control Mode section
of the dialog screen enter the desired
"Close Inverse Time" (60 to 3600
Seconds) setting.
9. From the Auto Control Mode section
of the dialog screen enter the desired
"Open Inverse Time" (60 to 3600
Seconds) setting.
10. Select "Save". CapTalk will display a
"Confirm Writing to Device" confirmation
screen (Figure 4‑2).
11. Select "OK". CapTalk will display a
"Setpoints Successfully Written to
Control" confirmation screen (Figure
4‑14).
Summary of Contents for M-6280A
Page 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Page 33: ...This Page Left Intentionally Blank ...
Page 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Page 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Page 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Page 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Page 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Page 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Page 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Page 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Page 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Page 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Page 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...